Output Devices

 

OptiLogic OL 2108
Relay Out Module

 

Outputs
8
Card Cage Power Required
375 mA
Output Type
Mechanical relay
Contact Resistance
0.1 ohm (initial)
Contact Voltage Rating
0 - 60 VDC
0 - 120 VAC
Status Indicators
Logic Side LED
Contact Rating
2A @ 24 VDC (resistive)/point, 1A @ 120 VAC
Terminal Strip
Plug In (removable)
Contact Type
Form A (SPST)
Terminal Screws
Slotted (0.1" blade max.)
Minimum Load
10 mA
Maximum Terminal Wire Gauge
18 AWG
Contact Arrangement
4 relays per common
Weight
2.1 oz. (58 g)
Mechanical Life 10,000,000 operations per relay (at no load) Electrical Life 100,000 operations per relay (at full load)
Type 9 Subtype 1

 

 

   

 